U/UTP CAT.6A ULTRA SUPER SLIM LSZH ECA

CABLE CONSTRUCTION
Conductor: The conductors shall be solid, annealed and bare copper with a diameter of AWG26
Insulation: Each conductor shall be insulated with solid high density polyethylene. The insulation shall be uniform and shall not have any defects.
Sheath: The flame retardant PVC or LSZH(Low Smoke Zero Halogen) compound colored grey or other colors shall be applied over the cable core.
ELECTRICAL PERFORMANCE
Characteristics Units Specification
DC Resistance Ω/100m ≤ 14.8
DC Resistance Unbalance % ≤ 2.00
Capacitance Unbalance
(Pair to Ground)
pF/km
(800~1000Hz)
≤ 1600
Insulation Resistance MΩ-100m ≥ 5000
Dielectric Strength DC kV/sec 2.5 / 2
Impedance

(Characteristic mean)

Ω 100 ± 5% (at 100MHz)
Return Loss dB/100m ≥ 20 + 5 * log(freq)         , 4      ≤ f <  10MHz
≥ 25                                   , 10  ≤ f < 20MHz
≥ 25 – 8.6* log(freq/20) , 20  ≤ f ≤ 500MHz
Attenuation
(Insertion Loss)
dB/100m ≤ 2.73*√(freq) + 0.0136*(freq) + 0.375/√(freq)
, 4 ~ 500 MHz
NEXT Loss dB/100m ≥ 75.3 – 15*log(freq) , 4 ~ 500MHz
Power sum NEXT Loss dB/100m ≥ 72.3 – 15*log(freq) , 4 ~ 500MHz
ACRF Loss dB/100m ≥ 68 – 20*log(freq) , 4 ~ 500MHz
Power sum ACRF Loss dB/100m ≥ 61 – 20*log(freq) ,4 ~ 100MHz
Propagation Delay dB/100m ≤ 534 + 36 / √ (Freq) , 4 ~ 500MHz
Propagation Delay Skew dB/100m ≤ 45 , 4 ~ 500MHz
FLAME REQUIREMENTS
– The LSZH(CMX) product comply with CPR reaction to fire : Eca