Conductor: The conductors shall be solid, annealed and bare copper with a diameter of AWG23.
Insulation: Each conductor shall be insulated with HDPE. The insulation shall be uniform and shall not have any defects. The diameter over the insulation shall be maximum 1.22mm.
Non-continuous Shield: The non-continuous aluminum tape shall be applied over the core wrapping to increase alien crosstalk performances.
ELECTRICAL PERFORMANCE
Characteristics Units Specification
DC Resistance Ω/100m ≤ 9.38
DC Resistance Unbalance % ≤ 5.00
Capacitance Unbalance
(Pair to Ground)
pF/km ≤ 330
Insulation Resistance MΩ-100m ≥ 500
Dielectric Strength DC kV/sec 2.5 / 2
Impedance

(Characteristic mean)

Ω 100 ± 15% (1 ≤ f ≤ 500MHz)
Return Loss dB/100m ≥ 20 + 5 * log(freq)         , 1      ≤ f <  10MHz
≥ 25                                   , 10  ≤ f < 20MHz
≥ 25 – 7 * log(freq/20) , 20  ≤  f ≤  500MHz
Attenuation
(Insertion Loss)
dB/100m ≤ 1.82*√(freq) + 0.0091*(freq) + 0.25/√(freq)
, 1 ~ 500 MHz
NEXT Loss dB/100m ≥ 44.3 – 15*log(freq/100) , 1 ~ 500MHz
Power sum NEXT Loss dB/100m ≥ 42.3 – 15*log(freq/100) , 1 ~ 500MHz
ELFEXT Loss dB/100m ≥ 27.8 – 20*log(freq/100) , 1 ~ 500MHz
Power sum ELFEXT Loss dB/100m ≥ 24.8 – 20*log(freq/100) , 1 ~ 500MHz
Propagation Delay dB/100m ≤ 534 + 36 / √ (Freq) , 1 ~ 500MHz
Propagation Delay Skew dB/100m ≤ 45 , 1 ~ 500MHz
CPR COMPLIANT
The LSZH product comply with CPR reaction to fire : Cca