U/UTP CAT.6 PVC ECA

CABLE CONSTRUCTION
Conductor: The conductors shall be solid, annealed and bare copper with a diameter of AWG23~24 and minimum acceptable diameter shall be 0.485mm.
Inuslation: Each conductor shall be insulated with solid high density polyethylene or FEP(only CMP cable). The insulation shall be uniform and shall not have any defects.
Sheath: The flame retardant PVC or LSZH(Low Smoke Zero Halogen) compound colored grey or other colors shall be applied over the cable core.
ELECTRICAL PERFORMANCE
Characteristics Units Specification
DC Resistance Ω/100m ≤ 9.38
DC Resistance Unbalance % ≤ 5.00
Capacitance Unbalance
(Pair to Ground)
pF/km ≤ 330
Insulation Resistance MΩ-100m ≥ 500
Dielectric Strength DC kV/sec 2.5 / 2
Impedance

(Characteristic mean)

Ω 100 ± 15%  (1 ≤ f ≤ 250MHz)
Return Loss dB/100m ≥ 20 + 5 * log(freq)         , 1      ≤ f <  10MHz
≥ 25                                   , 10  ≤ f < 20MHz
≥ 25 – 7 * log(freq/20) , 20  ≤ f ≤ 250MHz
Attenuation
(Insertion Loss)
dB/100m ≤ 1.808*√(freq) + 0.017*(freq) + 0.20/√(freq)
, 1 ~ 250 MHz
NEXT Loss dB/100m ≥ 44.3 – 15*log(freq/100) , 1 ~ 250MHz
Power sum NEXT Loss dB/100m ≥ 42.3 – 15*log(freq/100) , 1 ~ 250MHz
ELFEXT Loss dB/100m ≥ 27.8 – 20*log(freq/100) , 1 ~ 250MHz
Power sum ELFEXT Loss dB/100m ≥ 24.8 – 20*log(freq/100) , 1 ~ 250MHz
Propagation Delay dB/100m ≤ 534 + 36 / √(Freq) , 1 ~ 250MHz
Propagation Delay Skew dB/100m ≤ 45
FLAME REQUIREMENTS
A cable marked CMX shall comply with the VW-1 flame test specified in section 1080 of UL 1581 or IEC 60332-1.
A cable marked CM shall comply with the vertical flame test specified in UL 1685 or IEC 60332-3.
A cable marked CMR shall comply with the riser test specified in UL 1666.
A cable marked CMP shall comply with the CMP test specified in NFPA 262.